Microprocessor based AMF controller for DG Set with 3 Analog channels. Low Lube Oil Pressure Sensor, High Water Temperature Sensor, Low Fuel Level Sensor, RS485 Communication.
GET A QUOTE View/Download CatalogueSpecifications | |
---|---|
Analog input | Low Lube Oil Pressure Sensor, High Water Temperature Sensor, Low Fuel Level Sensor. |
Cyclic Operation | ECON can be programmed to automatically shut down the engine, for a predefined duration, after a redefined duration of operation, even if the mains is unhealthy. In case the mains continue to be unhealthy this cyclic operation will continue till the mains is restored. |
DG in Various Mode | Auto Mode, Semi Auto Mode, Auto Stop Mode. |
Load Management | ECON-A has programmable contact Load management function. The load management contact will switch on when the current on the generator has crossed a programmed limit and will reset when the current has fallen below the reset programmed limit. This function can be used to cut-off unnecessary loads or start a second generator when the load goes above a limit. |
Event Recording | ECON keeps a log of last 64 events. Setting change and warning are considered as event. Events are stamped along with date and time. |
Communication | RS485 |